015 - Fire
UNKNOWN
USE-#23-MIN REQ FIRE FLOWStatus
Minimum required fire flow shall be 1000 GPM for a 2 hour duration at 20 PSI residual operating pressure, which must be available before any combustible material is placed on the job site.
015 - Fire
UNKNOWN
USE-#50-BLUE DOT REFLECTORStatus
Blue retroreflective pavement markers shall be mounted on private street, public streets and driveways to indicate location of fire hydrants. Prior to installation, placement of markers must be approved by the Riverside County Fire Department.
015 - Fire
UNKNOWN
USE-#76-STANDARD FH 330/165Status
A Approved standard fire hydrant (6"x4"x2 1/2") shall be located within 250 feet of any portion of the lot frontage.
015 - Flood
UNKNOWN
USE ELEVATE FINISH FLOORStatus
The finished floor of new structures shall be elevated 12 inches above the highest adjacent ground (i.e., at least to the elevation of 1008.9).
015 - Flood
UNKNOWN
USE FLOOD HAZARD REPORTStatus
PP24278 proposes to construct 4,000 square-feet accessory structure, about 3600 square-feet driveway, and about 8,000 square-feet of pad (use unknown) on an existing development located at 16375 Fox Gen Drive in the Mockingbird area. The existing improvement (residence, driveway and horse barn) on the site is approximately 10,000 square-feet. Since the proposed impervious improvement is more than 5000 square feet, a preliminary project specific Water Quality Management Plan (WQMP) is required. The District has received a preliminary WQMP on March 30, 2010 and some additional calculations were submitted on June 17, 2010. The water quality plan proposes an infiltration trench and a grassy swale on the north western corner along Fox Glen Road and Mockingbird Canyon Road. Conceptually this is acceptable to the District but for final WQMP the developer shall submit a tentative exhibit and a BMP exhibit with proposed BMP and the cross section shown on it. At final plan check the developer may need larger infiltration trench but the site has enough area to accommodate it and therefore the District has no objection to this proposal. The finished floor of the structure shall be constructed to a minimum of 1 foot above adjacent ground (i.e., at least to the elevation of 1008.9)
015 - Flood
UNKNOWN
USE SUBMIT FINAL WQMP >PRELIMStatus
In compliance with Santa Ana Region and San Diego Region Regional Water Quality Control Board Orders, and Beginning January 1, 2005, projects submitted within the western region of the unincorporated area of Riverside County for discretionary approval will be required to comply with the Water Quality Management Plan for Urban Runoff (WQMP). The WQMP addresses post-development water quality impacts from new development and redevelopment projects. The WQMP requirements will vary depending on the project's geographic location (Santa Ana, Santa Margarita or Whitewater River watersheds). The WQMP provides detailed guidelines and templates to assist the developer in completing the necessary studies. These documents are available on-line at: www.rcflood.org/NPDES under Programs and Services, Stormwater Quality. To comply with the WQMP a developer must submit a "Project Specific" WQMP. This report is intended to a) identify potential post-project pollutants and hydrologic impacts associated with the development; b) identify proposed mitigation measures (BMPs) for identified impacts including site design, source control and treatment control post-development BMPs; and c) identify sustainable funding and maintenance mechanisms for the aforementioned BMPs. A template for this report is included as 'exhibit A' in the WQMP. A final Project Specific WQMP must be approved by the District prior to issuance of building or grading permits. Projects requiring Project Specific WQMPs are required to submit a PRELIMINARY Project Specific WQMP along with the land-use application package. The format of the PRELIMINARY report shall mimic the format/template of the final report but can be less detailed. For example, points a, b & c above must be covered, rough calculations supporting sizing must be included, and footprint/locations for the BMPs must be identified on the tentative exhibit. Detailed drawings will not be required. This preliminary project specific WQMP must be approved by the District prior to issuance of recommended conditions of approval. The developer has submitted a report that minimally meets the criteria for a preliminary project specific WQMP. The report will need significant revisions to meet the requirements of a final project specific WQMP. Also, it should be noted that if 401 certification is necessary for the project, the Water Quality Control Board may require additional water quality measures.
015 - Flood
UNKNOWN
USE WQMP ESTABL MAINT ENTITYStatus
This project proposes BMP facilities that will require maintenance by public agency or commercial property owner association. To ensure that the public is not unduly burdened with future costs, prior to final approval or recordation of this case, the District will require an acceptable financial mechanism be implemented to provide for maintenance of treatment control BMPs in perpetuity. This may consist of a mechanism to assess individual benefiting property owners, or other means approved by the District. The site's treatment control BMPs must be shown on the project's improvement plans - either the street plans, grading plans, or landscaping plans. The type of improvement plans that will show the BMPs will depend on the selected maintenance entity.
015 - Planning
UNKNOWN
PPA - ACSRY STRC NO HBTBL AREAStatus
No habitable area has been approved with this approval. The addition of habitable area will require additional approvals.
015 - Planning
UNKNOWN
PPA - LANDUSE APPROVAL ONLYStatus
The applicant or the applicant's successor in interest is notified through this condition that the approval granted on Plot Plan No. 24278 is for land use approval only, and has only met the requirements of Ordinance 348. Any requirements deemed necessary by another department or agency of Riverside County on a subsequent building permit are valid and may cause this approval by the Riverside County Planning Department as it stands to be rendered null and void or require significant revision. It is incumbent upon the applicant to research the acceptability of this proposal to all responsible departments and agencies prior to the acceptance of this approval. Responsible agencies include, but are not limited to the Fire Department, Environmental Health Department, the local Flood Control District, Building and Safety Department, Transportation Department, the Environmental Programs Department, the County Geologist, or the Transportation Land Management Agency.
015 - Planning
UNKNOWN
PPA - NO COMMERCIAL USEStatus
The subject accessory structure shall not be used for commercial, industrial, manufacturing, or other non-residential use. No commercial, industrial, or manufacturing storage shall be allowed on subject property.
015 - Planning
UNKNOWN
PPA - NO HOME OCCUPATIONSStatus
No home occupations are permitted in an accessory structure or guest home. From section 21.36 of Ordinance 348: Home Occupations: Home occupations means those uses that are customarily conducted in a residence, provided such uses must be incidental and secondary to the principal use of a dwelling as a residence. The following criteria shall apply to any home occupation: a. Except for large family day care homes which may require two assistants and small family day care homes which may require one assistant to be present in addition to the licensee or provider, no person other than a resident of the dwelling shall be employed on the premises in the conduct of a home occupation. b. A home occupation shall be conducted entirely within the dwelling and shall be incidental and secondary to the use of the dwelling as a residence. c. A home occupation shall not be conducted in an accessory structure and there shall be no storage of equipment or supplies in an accessory structure or outside building. d. The residential character of the exterior and interior of the dwelling shall not be changed. e. No vehicles or trailers except those normally incidental to residential use shall be kept on the site. f. No signs other than one unlighted identification sign, not more than two square feet in area, shall be erected on the premises.
015 - Planning
UNKNOWN
PPA - SETBACKS IN HIGH FIREStatus
Please be advised that the setbacks for structures within a County designated high fire areas have increased. It is advisable prior to the purchase of structure or prior to planning of a structure (such as hiring an architect or engineer to create plans) that the applicant should contact the Fire Department to make sure that the structure question meets those requirements. Fire Department Planning 2300 Market Street, Suite 150 Riverside, CA 92501 951-955-4777
015 - Planning
UNKNOWN
PPA - EXISTING STRUCTURE (1)Status
WITHIN SIXTY (60) DAYS OF THE EFFECTIVE DATE OF THIS PERMIT, the permittee or the permittee's successors-in- interest shall apply to the Building and Safety Department for all necessary permits, including the submission of all required documents and fees for any plan check review as determined by the Director of the Department of Building and Safety, to ensure that all existing buildings, structures and uses are in compliance with Ordinance No. 348 and Ordinance No. 457 and the conditions of approval of this permit.
015 - Planning
UNKNOWN
PPA - EXPIRATION DATE-PPStatus
This approval shall be used within two (2) years of approval date; otherwise, it shall become null and void and of no effect whatsoever. By use is meant the beginning of substantial construction comtemplated by this approval within a two (2) year period which is thereafter diligently pursued to completion or to the actual occupancy of exisiting buildings or land under the terms of the authorized use. Prior to the expiration of the two year period, the permittee may request a one (1) year extension of time request in which to use this plot plan. A maximum of three one-year extension of time requests shall be permitted. Should the time period established by any of the extension of time requests lapse, or should all three one-year extensions be obtained and no substantial construction or use of this plot plan be initiated within five (5) years of the effective date of the issuance of this plot plan, this plot plan shall become null and void.
015 - Planning-All
UNKNOWN
All-PPA - DEFINITIONSStatus
The words identified in the following list that appear in all capitals in the attached conditions of Plot Plan No. PP24278 shall be henceforth defined as follows: APPROVED EXHIBIT A = Plot Plan No. 24278, Exhibit A, Amended No. 1, dated November 16, 2009.
015 - Planning-All
UNKNOWN
All-PPA - HOLD HARMLESSStatus
The applicant/permittee or any successor-in-interest shall defend, indemnify, and hold harmless the County of Riverside COUNTY), its agents, officers, or employees from any claim, action, or proceeding against the COUNTY, its agents, officers, or employees to attack, set aside, void, or annul an approval of the COUNTY, its advisory agencies, appeal boards, or legislative body concerning PP24278. The COUNTY will promptly notify the applicant/ permittee of any such claim, action, or proceeding against the COUNTY and will cooperate fully in the defense. If the COUNTY fails to promptly notify the applicant/permittee of any such claim, action, or proceeding or fails to cooperate fully in the defense, the applicant/permittee shall not, thereafter, be responsible to defend, indemnify, or hold harmless the COUNTY.
015 - Planning-All
UNKNOWN
All-PPA - PROJECT DESCRIPTIONStatus
The use hereby permitted is the construction of a 2,000 square foot detached metal storage building on 2.25 Acres, associated with the 3,472 square foot residence located at 16375 Fox Glen Road in Riverside, CA. APN: 285-280-015.
060 - Flood
Prior To Grading Permit Issuance
USE SUBMIT FINAL WQMPStatus
A copy of the project specific WQMP shall be submitted to the District for review and approval.
060 - Flood
Prior To Grading Permit Issuance
USE SUBMIT PLANS MINOR REVIEWStatus
The scope of the District review will be limited to verification that this proposal has met its obligation under the County's municipal stormwater permit. A copy of the BMP improvement plans along with any necessary documentation shall be submitted to the Districts Plan Check Section for review. A copy of the improvement and grading plans shall be included for reference. The plans must receive the District's approval prior to issuance of permits. All submittals shall be date stamped by the engineer and include a completed Flood Control Deposit Based Fee Worksheet and the appropriate plan check fee deposit.
080 - Fire
Prior To Building Permit Issuance
USE-#4-WATER PLANSStatus
The applicant or developer shall separately submit two copies of the water system plans to the Fire Department for review and approval. Calculated velocities shall not exceed 10 feet per second. Plans shall conform to the fire hydrant types, location and spacing, and the system shall meet the fire flow requirements. Plans shall be signed and approved by a registered civil engineer and the local water company with the following certification: "I certify that the design of the water system is in accordance with the requirements prescribed by the Riverside County Fire Department."
080 - Flood
Prior To Building Permit Issuance
USE SUBMIT FINAL WQMPStatus
A copy of the project specific WQMP shall be submitted to the District for review and approval.
080 - Flood
Prior To Building Permit Issuance
USE SUBMIT PLANS MINOR REVIEWStatus
The scope of the District review will be limited to verification that this proposal has met its obligation under the County's municipal stormwater permit. A copy of the BMP improvement plans along with any necessary documentation shall be submitted to the Districts Plan Check Section for review. A copy of the improvement and grading plans shall be included for reference. The plans must receive the District's approval prior to issuance of permits. All submittals shall be date stamped by the engineer and include a completed Flood Control Deposit Based Fee Worksheet and the appropriate plan check fee deposit.
080 - Planning
Prior To Building Permit Issuance
PPA - AMENDED EXHIBITSStatus
Applicant to submit amended site plan with elevation and floor plans for the 2,000 square foot metal building. The amended site plan shall reflect the footpint, setback and location of structure.
080 - Planning
Prior To Building Permit Issuance
PPA - CONFORM TO ELEVATIONSStatus
Elevations of all buildings and structures submitted for building plan check approval shall be in substantial conformance with the elevations shown on APPROVED EXHIBIT B, Amended No. 1, dated November 16, 2009,
080 - Planning
Prior To Building Permit Issuance
PPA - CONFORM TO FLOOR PLANSStatus
Floor plans shall be in substantial conformance with that shown on APPROVED EXHIBIT C, Amended No. 1, dated November 16, 2009.
080 - Planning
Prior To Building Permit Issuance
PPA - EXISTING STRUCTUREStatus
PRIOR TO BUILDING PERMIT ISSUANCE, the permittee or the permittee's successors-in- interest shall apply to the Building and Safety Department for all necessary permits, including the submission of all required documents and fees for any plan check review as determined by the Director of the Department of Building and Safety, to ensure that all existing buildings, structures and uses are in compliance with Ordinance No. 348 and Ordinance No. 457 and the conditions of approval of this permit.
090 - Fire
Prior to Building Final Inspection
USE-#12A-SPRINKLER SYSTEMStatus
Install a complete fire sprinkler system per NFPA 13D 2002 edition.Plans must be submitted to the Fire Dept. for review and approval prior to installation.
090 - Fire
Prior to Building Final Inspection
USE-#27-EXTINGUISHERSStatus
nstall portable fire extinguishers with a minimum rating of 2A-10BC and signage. Fire Extinguishers located in public areas shall be in recessed cabinets mounted 48" (inches) to center above floor level with maximum 4" projection from the wall. Contact Fire Department for proper placement of equipment prior to installation.
090 - Flood
Prior to Building Final Inspection
USE BMP - EDUCATIONStatus
The developer shall distribute environmental awareness education materials on general good housekeeping practices that contribute to protection of stormwater quality to all initial users. The developer may obtain NPDES Public Educational Program materials from the District's website: www.rcwatershed.org/about/materials-library. The developer must provide to the District's Plan Check Department a notarized affidavit stating that the distribution of educational materials to the tenants is assured prior to the issuance of occupancy permits. If conditioned for a Water Quality Management Report (WQMP), a copy of the notarized affidavit must be placed in the report. The District MUST also receive the original notarized affidavit with the plan check submittal, by mail or in person in order to clear the appropriate condition. Placing a copy of the affidavit in the WQMP without submitting the original will not guarantee clearance of the condition.
090 - Flood
Prior to Building Final Inspection
USE BMP MAINTENANCE & INSPECTStatus
The BMP maintenance plan shall contain provisions for all treatment controlled BMPs to be inspected, and if required, cleaned no later than October 15 each year. Required documentation shall identify the entity that will inspect and maintain all structural BMPs within the project boundaries. A copy of all necessary documentation shall be submitted to the District for review and approval prior to the issuance of occupancy permits.
090 - Flood
Prior to Building Final Inspection
USE IMPLEMENT WQMPStatus
All structural BMPs described in the project-specific WQMP shall be constructed and installed in conformance with approved plans and specifications. It shall be demonstrated that the applicant is prepared to implement all non-structural BMPs described in the approved project specific WQMP and that copies of the approved project-specific WQMP are available for the future owners/occupants. The District will not release occupancy permits for any portion of the project exceeding 80% of the project area prior to the completion of these tasks.
090 - Planning
Prior to Building Final Inspection
PPA - GRADING DOCUMENTSStatus
Applicant to submit copies of all final grading report and/or approval letters to Planning Department for verification of compliance. A copy to be placed in case file