015 - Fire UNKNOWN | USE-#20-STANDARD FIRE HYDRANT | Status
|
| A standard fire hydrant(6"x4"x 2-2 1/2") shall be located
within 250 feet of any portion of the lot frontage as
measured along approved vehicular travel ways.
|
015 - Fire UNKNOWN | USE-#23-MIN REQ FIRE FLOW | Status
|
| Minimum required fire flow shall be 1000 GPM for a 2 hour
duration at 20 PSI residual operating pressure.
|
015 - Fire UNKNOWN | USE-#25-GATE ENTRANCES | Status
|
| ny gate providing access from a road to a driveway shall be
located at least 35 feet from the roadway and shall open to
allow a vehicle to stop without obstructing traffic on the
road. Where a one-way road with a single traffic lane
provides access to a gate entrance, a 38 foot turning
radius shall be used.
|
015 - Fire UNKNOWN | USE-#50-BLUE DOT REFLECTOR | Status
|
| Blue retroreflective pavement markers shall be mounted on
private street, public streets and driveways to indicate
location of fire hydrants. Prior to installation, placement
of markers must be approved by the Riverside County Fire
Department.
|
015 - Fire UNKNOWN | USE-#88A-AUTO/MAN GATES | Status
|
| Gate(s) shall be
automatic operated, minimum 20 feet in width, with a
setback of 35 feet from face of curb/flow line. Gate
access shall be equipped with a rapid entry system. Plans
shall be submitted to the Fire Department for approval
prior to installation. Automatic/manual gate pins shall be
rated with shear pin force, not to exceed 30 foot pounds.
Automatic gates shall be equipped with emergency backup
power. Gates activated by the rapid entry system shall
remain open until closed by the rapid entry system.
|
015 - Planning UNKNOWN | PPA - ACSRY STRC NO HBTBL AREA | Status
|
| No habitable area has been approved with this approval.
The addition of habitable area will require additional
approvals.
|
015 - Planning UNKNOWN | PPA - LANDUSE APPROVAL ONLY | Status
|
| The applicant or the applicant's successor in interest is
notified through this condition that the approval granted
on Plot Plan No. 24127 is for land use approval only, and
has only met the requirements of Ordinance 348. Any
requirements deemed necessary by another department or
agency of Riverside County on a subsequent building permit
are valid and may cause this approval by the Riverside
County Planning Department as it stands to be rendered null
and void or require significant revision. It is incumbent
upon the applicant to research the acceptability of this
proposal to all responsible departments and agencies prior
to the acceptance of this approval. Responsible agencies
include, but are not limited to the Fire Department,
Environmental Health Department, the local Flood Control
District, Building and Safety Department, Transportation
Department, the Environmental Programs Department, the
County Geologist, or the Transportation Land Management
Agency.
|
015 - Planning UNKNOWN | PPA - NO HOME OCCUPATIONS | Status
|
| No home occupations are permitted in an accessory structure
or guest home.
From section 21.36 of Ordinance 348: Home Occupations:
Home occupations means those uses that are customarily
conducted in a residence, provided such uses must be
incidental and secondary to the principal use of a dwelling
as a residence. The following criteria shall apply to any
home occupation:
a. Except for large family day care homes which may require
two assistants and small family day care homes which may
require one assistant to be present in addition to the
licensee or provider, no person other than a resident of
the dwelling shall be employed on the premises in the
conduct of a home occupation.
b. A home occupation shall be conducted entirely within the
dwelling and shall be incidental and secondary to the use
of the dwelling as a residence.
c. A home occupation shall not be conducted in an accessory
structure and there shall be no storage of equipment or
supplies in an accessory structure or outside building.
d. The residential character of the exterior and interior
of the dwelling shall not be changed.
e. No vehicles or trailers except those normally incidental
to residential use shall be kept on the site.
f. No signs other than one unlighted identification sign,
not more than two square feet in area, shall be erected on
the premises.
|
015 - Planning UNKNOWN | PPA - SETBACKS IN HIGH FIRE | Status
|
| Please be advised that the setbacks for structures within a
County designated high fire areas have increased. It is
advisable prior to the purchase of structure or prior to
planning of a structure (such as hiring an architect or
engineer to create plans) that the applicant should contact
the Fire Department to make sure that the structure
question meets those requirements.
Fire Department Planning
2300 Market Street, Suite 150
Riverside, CA 92501
951-955-4777
|
015 - Planning UNKNOWN | PPA - EXISTING STRUCTURE (1) | Status
|
| WITHIN SIXTY (60) DAYS OF THE EFFECTIVE DATE OF THIS
PERMIT, the permittee or the permittee's successors-in-
interest shall apply to the Building and Safety Department
for all necessary permits, including the submission of all
required documents and fees for any plan check review as
determined by the Director of the Department of Building
and Safety, to ensure that all existing buildings,
structures and uses are in compliance with Ordinance No.
348 and Ordinance No. 457 and the conditions of approval
of this permit.
|
015 - Planning UNKNOWN | PPA - EXPIRATION DATE-PP | Status
|
| This approval shall be used within two (2) years of
approval date; otherwise, it shall become null and void and
of no effect whatsoever. By use is meant the beginning of
substantial construction comtemplated by this approval
within a two (2) year period which is thereafter diligently
pursued to completion or to the actual occupancy of
exisiting buildings or land under the terms of the
authorized use. Prior to the expiration of the two year
period, the permittee may request a one (1) year extension
of time request in which to use this plot plan. A maximum
of three one-year extension of time requests shall be
permitted. Should the time period established by any of
the extension of time requests lapse, or should all three
one-year extensions be obtained and no substantial
construction or use of this plot plan be initiated within
five (5) years of the effective date of the issuance of
this plot plan, this plot plan shall become null and void.
|
015 - Planning-All UNKNOWN | All-PPA - DEFINITIONS | Status
|
| The words identified in the following list that appear in
all capitals in the attached conditions of Plot Plan
No. A shall be henceforth defined as follows:
APPROVED EXHIBIT A = Plot Plan No. 24127, Exhibit A, dated
October 27, 2009.
|
015 - Planning-All UNKNOWN | All-PPA - HOLD HARMLESS | Status
|
| The applicant/permittee or any successor-in-interest shall
defend, indemnify, and hold harmless the County of
Riverside COUNTY), its agents, officers, or employees from
any claim, action, or proceeding against the COUNTY, its
agents, officers, or employees to attack, set aside, void,
or annul an approval of the COUNTY, its advisory agencies,
appeal boards, or legislative body concerning PP24127. The
COUNTY will promptly notify the applicant/ permittee of
any such claim, action, or proceeding against the COUNTY
and will cooperate fully in the defense. If the COUNTY
fails to promptly notify the applicant/permittee of any
such claim, action, or proceeding or fails to cooperate
fully in the defense, the applicant/permittee shall not,
thereafter, be responsible to defend, indemnify, or hold
harmless the COUNTY.
|
015 - Planning-All UNKNOWN | All-PPA - PROJECT DESCRIPTION | Status
|
| The use hereby permitted is a RV garage/storage building
1st floor 3,960 square feet and 2nd floor 1,582 square
feet, 324 square foot free-standing gazebo and Variance No.
1836 to construct building 21 feet from road right of way
on .73 acre with existing 1,642 square foot residence
located at 2007 Gail Drive in Riverside, CA. APN:
175-320-009
|
015 - Planning-All UNKNOWN | All-USE - SC1 DEFINITIONS | Status
|
| The words identified in the following list that appear in
all capitals in the attached conditions of Plot Plan No.
PP24127S1 shall be henceforth defined as follows:
APPROVED EXHIBIT A = Plot Plan No. 24127S1, Exhibit A,
Amended No. 2, dated 2/7/12.
APPROVED EXHIBIT B = Plot Plan No. 24127S1, Exhibit B,
Amended No. 2. dated 2/7/12.
APPROVED EXHIBIT C = PLOT PLAN NO. 24127S1, EXHIBIT C,
Amended No. 2, dated 2/7/12.
|
015 - Planning-All UNKNOWN | All-USE - SC1 PROJECT DESCRITION | Status
|
| The use hereby permitted is a re-configuration of the
interior space pf the approved PP24127 for a two story
6,912 detached RV garage.
First Floor:
3,711.8 square feet of garage area. 599.4 square feet of
workshop area. 392.8 square feet of storage and stairwell.
Second Floor:
1,610 square feet of storage. 598 square feet of guest
quarters with stairs.
Totaling: 6,912 square feet.
|
080 - Fire Prior To Building Permit Issuance | USE-#4-WATER PLANS | Status
|
| The applicant or developer shall separately submit two
copies of the water system plans to the Fire Department for
review and approval. Calculated velocities shall not exceed
10 feet per second. Plans shall conform to the fire hydrant
types, location and spacing, and the system shall meet the
fire flow requirements.
Plans shall be signed and approved by a registered civil
engineer and the local water company with the following
certification: "I certify that the design of the water
system is in accordance with the requirements prescribed by
the Riverside County Fire Department."
|
080 - Planning Prior To Building Permit Issuance | PPA - CONFORM TO ELEVATIONS | Status
|
| Elevations of all buildings and structures submitted for
building plan check approval shall be in substantial
conformance with the elevations shown on APPROVED EXHIBIT
A-4 and A-5, dated October 27, 2009.
|
080 - Planning Prior To Building Permit Issuance | PPA - CONFORM TO FLOOR PLANS | Status
|
| Floor plans shall be in substantial conformance with that
shown on APPROVED EXHIBIT A-2 and A-3, dated October 27,
2009.
|
080 - Planning Prior To Building Permit Issuance | PPA - EXISTING STRUCTURE | Status
|
| PRIOR TO BUILDING PERMIT ISSUANCE, the permittee or the
permittee's successors-in- interest shall apply to the
Building and Safety Department for all necessary permits,
including the submission of all required documents and fees
for any plan check review as determined by the Director of
the Department of Building and Safety, to ensure that all
existing buildings, structures and uses are in compliance
with Ordinance No. 348 and Ordinance No. 457 and the
conditions of approval of this permit.
|
090 - Fire Prior to Building Final Inspection | USE-#12A-SPRINKLER SYSTEM | Status
|
| Install a complete fire sprinkler system per NFPA 13D 2002
edition.Plans must be submitted to the Fire Dept. for
review and approval prior to installation
|
090 - Fire Prior to Building Final Inspection | USE-#27-EXTINGUISHERS | Status
|
| nstall portable fire extinguishers with a minimum rating of
2A-10BC and signage. Fire Extinguishers located in public
areas shall be in recessed cabinets mounted 48" (inches) to
center above floor level with maximum 4" projection from
the wall. Contact Fire Department for proper placement of
equipment prior to installation.
|